Measures and Precautions to Prevent Freeze Damage to Heat Exchange Tubes
22-06-07




Shell-and-tube heat exchangers used in refrigeration systems frequently experience failures—often resulting in system shutdown and substantial economic losses—due to the rupture of heat exchange tubes. One of the most common causes of such tube ruptures is the expansion of ice formed on the water side inside the heat exchanger, which can either burst or crush the tubes. Typically, condensers and flooded evaporators are more prone to damage caused by ice-induced tube bursting, whereas dry-type evaporators are more likely to suffer from ice-induced tube crushing. The primary causes of water freezing inside heat exchangers and the corresponding preventive measures are outlined below.
- The system group has been shut down for an extended period, yet the water has not been drained or has not been completely drained. When the ambient temperature drops below... 0 After the system is shut down, the water remaining in the heat exchange tubes can freeze and expand, potentially rupturing the tubes. To prevent this from happening, users must ensure that all water is completely drained from the heat exchangers when the system is shut down for an extended period. Drain valves or drain plugs are installed at the lower portions of the water chamber end caps of both the condenser and flooded-type evaporators, as well as at the lower part of the shell of dry-type evaporators, allowing maintenance personnel to drain the water from the heat exchangers through these openings. For air-cooled heat pump systems, during winter operation, there may be instances where the system is briefly shut down. However, in such cases, the ambient temperature is low, causing the water temperature to drop rapidly below the freezing point. Although frequent manual draining by maintenance staff can be inconvenient, it is recommended for such systems to adopt an antifreeze operating control mode. In the system shutdown mode, the antifreeze mode can be activated automatically. When the water temperature falls below a certain threshold, the control system will automatically start the water pump to circulate the water. If the water temperature continues to drop, the system will automatically switch to heating mode, activating the compressor until the water temperature rises back into a safe range.
- When servicing equipment, failing to completely drain the water from the heat exchanger or to turn on the water pump to keep the water flowing before recovering and recharging the refrigerant can cause the refrigerant to evaporate rapidly, absorbing heat from the water. Since the water inside the heat exchanger remains stagnant, it will quickly freeze, leading to rupture and damage of the heat exchange tubes. To prevent such situations, equipment maintenance personnel must ensure that refrigerant recovery and recharge operations are performed only when the heat exchanger is either completely empty of water or when the water is actively flowing.
- Insufficient refrigerant charge or a refrigerant leak within the refrigeration system can lead to an abnormal evaporation pressure and cause the evaporation temperature to remain consistently low. 0 When operating below the specified temperature, icing tends to occur in the evaporator—particularly at low water flow rates and in stagnant water zones—resulting in ice-induced bulging or damage to the heat exchanger tubes. To prevent such situations, it is essential that the refrigeration system be adequately charged with refrigerant and equipped with a low-pressure alarm device. An antifreeze switch should also be installed at the evaporator outlet. Additionally, equipment maintenance personnel must regularly monitor the system’s pressure levels to promptly detect any refrigerant leaks.
- Since the water system is not equipped with a flow-cut-off protection device, when the pump fails or for other reasons causes a sudden interruption in the water flow during equipment operation, the compressor system continues running without having sufficient time to reduce its load or shut down the system. Meanwhile, the refrigerant inside the evaporator keeps evaporating continuously. As a result, both the low-pressure protection device and the freeze-protection device often fail to react in time, causing the water in the evaporator to freeze. This freezing can lead to rupture and damage of the heat-exchange tubes. To prevent such situations, it is essential to install flow switches or differential-pressure switches—flow-cut-off protection devices—in the water system.
- Due to malfunctions in the equipment’s sensors or related protective devices, the system fails to promptly trigger an alarm and shut down when abnormal conditions occur. This is particularly true in cases where the temperature sensor malfunctions and cannot accurately reflect the actual temperature. When the actual water temperature reaches the load-reduction range or the system-shutdown range, but the sensor continues to indicate that the temperature remains within the normal or loading range, the water temperature will drop sharply—eventually leading to freezing and causing the heat-exchange tubes to rupture and become damaged. To prevent such situations, it is recommended to use high-precision, reliable temperature sensors for the outlet water temperature. Additionally, installing a freeze-protection sensor or temperature switch as a backup measure can provide double protection and help mitigate the risk of sensor failures. Furthermore, equipment maintenance personnel should regularly calibrate temperature sensors using precision thermometers. If a sensor is found to be inaccurate, it should be replaced promptly.
Miss Deng:18922776417
Mr. Huang:13450460020
Mr. Zhang:13922978523
Email:1536214764@qq.com/ 673047694@qq.com
Company Address: No. 15, Alley 2, North of Lianhe Road, Fulong Village, Shipai Town, Dongguan City
Copyright © 2021 Dongguan Ganghui Refrigeration & Mechanical Equipment Co., Ltd.
Power by:www.300.cn | SEO | Privacy Policy
Welcome to the official website of GangHui!