SM501-2 SM501-2L SM502-2 Smart Digital Display Motor Protector Operating Instructions
22-11-11
Model: SM 501-2 Intelligent Digital Display Motor Protector
Model: SM 501-2L Intelligent Digital Display Motor Protector
Model: SM 502-2 Intelligent Digital Display Motor Protector
(Overload, phase failure, and unbalance protection; two-channel control terminals)
(Overload, phase failure, and unbalance protection; two-channel control terminals)
(Overload, phase failure, unbalance protection, dual-channel control, phase sequence protection terminal)
★ Feature Introduction:
· Current display: Under normal operating conditions (Standby) Cyclically displays three-phase current values, with a switching interval of 3 seconds. After fault protection is triggered, it locks. Display the three-phase current values when a fault occurs, making it easier to identify the cause of the fault. 。
· Overload protection: When the current in any phase exceeds the set trip current, the protector will trip. Load.
· Phase-loss protection: When a phase loss or severe imbalance is detected. When the imbalance value exceeds 80%, the protector disconnects the load.
· Unbalance Protection: Formula: (Maximum value – Minimum value) ÷ Maximum value × 100% [Example: Phase A: 20A, Phase B: 25A, Phase C: 22A] ,Imbalance value= (25-20) ÷ 25 × 100% = 20%. When the detected imbalance exceeds the set value, the protector will activate. Disconnect the load.
· Phase-sequence protection: When the protector detects a phase error, or... 380V voltage phase sequence signal power failure or open circuit condition Under these circumstances, the protector disconnects the load. · Power-on delay: After each power-on reset, the load side outputs with a delay.
· Control end operating instructions: After power-on, the control... 1 closed, delayed ( Configurable, parameters E) After the timing ends, control 2 closes. If a protection event occurs... Protect, control 1 and control 2 are disconnected simultaneously.
★ Operation Procedure Instructions:
① Unlock: Press and hold the “Unlock/Settings” button for 3 seconds. Light up—now entering the parameter setting mode. 。
② Parameter Settings: Continue pressing the “Unlock/Set” key to cycle through the various parameter settings. Press “△” and “—”. Key to adjust parameter values. Small. Example: Screen display “F00,” where “F” is the parameter code and “00” is the numerical value corresponding to the parameter. The following is: Parameter Code Reference Table:
|
Parameter code |
Parameter Name |
Fan surround |
Factory settings |
|
Set electricity Flow Bright |
Set the overcurrent protection value Set |
2A to 95A (The overload current setting is generally set to be greater than the maximum phase display value) Current 5–10 A, subject to actual conditions) |
30.0A |
|
F |
Power-on delay time setting |
Power on from 0 to 9.9 minutes (0.1 minute = 6 seconds) After, F minutes later, control The end is closed. |
0.0 minutes |
|
H |
Unbalanced Protection Selection |
0–40% (When 0 is selected, unbalance protection is disabled.) Can ) |
30 |
|
C |
Skip the inrush current setting. |
1 second to 29 seconds |
5 seconds |
|
d |
Overload protection delay setting |
1 second to 29 seconds |
3 seconds |
|
P |
Automatic reset times |
0–99 times (0 = disable automatic reset function) |
3 times |
|
L |
Automatic reset interval time |
1 to 99 minutes |
3 minutes |
|
E |
Control 1 and control 2 are incorrect. The time to start the interval. |
0.1 minute to 9.9 minutes (0.1 minute = 6 seconds) |
0.1 minute |
③ Save parameters: Stay on the parameter setting screen without making any changes for 10 seconds, and the system will automatically return to the standby screen while saving the parameters.
④ Query parameters: Press the “Unlock/Set” key to cycle sequentially through the various parameters.
★Key Technical Specifications:
1. Power supply: AC 220V ±10% 50 Hertz ( AC 380V ±10% Optional )
2. Output contact power: Resistive AC 220V/3A
3. External dimensions: 125 wide mm × 86 high mm × 40 thick mm
★ How to recover from protected state:
Operating Manual for the Intelligent Digital Display Motor Protector
① Manual Reset: After the protector triggers a protection action, press the “Reset” button to clear the protection status. If the current still meets the protection trigger conditions, The protector will be protected again.
② Automatic reset: After the protector triggers a protection action, it will automatically reset every L minutes. If, after P automatic resets, the current remains full, The foot protection trigger condition will no longer automatically reset. (Both P and L parameters are adjustable; see the parameter table for details.)
★ Notes:
1. The three phase wires of the protected motor must each pass through one of the three holes in the current transformer.
2. During installation and commissioning, you must carefully read the operating manual and ensure that there is a corresponding... Operated by qualified professionals.
3. After the protector displays a fault, you must eliminate the fault before putting it back into operation; otherwise, you will be responsible for any resulting consequences.
Previous:
Miss Deng:18922776417
Mr. Huang:13450460020
Mr. Zhang:13922978523
Email:1536214764@qq.com/ 673047694@qq.com
Company Address: No. 15, Alley 2, North of Lianhe Road, Fulong Village, Shipai Town, Dongguan City
Copyright © 2021 Dongguan Ganghui Refrigeration & Mechanical Equipment Co., Ltd.
Power by:www.300.cn | SEO | Privacy Policy
Welcome to the official website of GangHui!