Blockage failure of the thermal expansion valve
22-09-08
Blockage failure of the thermal expansion valve
Blockage faults in the thermostatic expansion valves of refrigeration systems are common and can be categorized into “dirty blockage” and “ice blockage.” The primary cause of dirty blockage is the presence of impurities in the system, such as welding slag, copper chips, iron filings, and fibers. The cause of ice blockage is excessive moisture (humidity) in the system; sources of this moisture include:
1) During installation, the system’s vacuuming time was insufficient, and moisture inside the piping was not completely removed. Additionally, the welding quality at the pipe connections was poor, resulting in air leaks.
2) When charging the system with refrigerant, the air inside the connecting hose was not purged from the hose.
3) When replenishing lubricant to the system, air enters.
Methods for clearing blockages
So, how do we troubleshoot blockages? For dirty blockages, if the blockage isn't severe, simply replacing the dryer filter will suffice. However, if the blockage is very serious, you'll need to thoroughly clean out impurities from the system's piping, evacuate the system to remove any remaining air and moisture, and then recharge the refrigerant. As for minor ice blockages, you can apply a warm towel to the blocked area. But if the ice blockage is severe enough to affect the normal operation of the system, you'll have to replace the filter-drier, carefully remove any moisture from the system piping, evacuate the system again, and then recharge the refrigerant.
Previous:
Miss Deng:18922776417
Mr. Huang:13450460020
Mr. Zhang:13922978523
Email:1536214764@qq.com/ 673047694@qq.com
Company Address: No. 15, Alley 2, North of Lianhe Road, Fulong Village, Shipai Town, Dongguan City
Copyright © 2021 Dongguan Ganghui Refrigeration & Mechanical Equipment Co., Ltd.
Power by:www.300.cn | SEO | Privacy Policy
Welcome to the official website of GangHui!