Method for Determining and Performing Cleaning of Shell-and-Tube Evaporators
22-10-08
Shell-and-tube evaporators tend to accumulate scale on their pipes over prolonged use, leading to increased energy consumption of the unit. Therefore, the condenser should be regularly descaled. If scale is not removed in a timely manner, it will impair heat transfer efficiency, causing the condensing temperature to rise and reducing the cooling capacity of the unit. Now, let’s take a closer look at the methods for determining when a shell-and-tube evaporator needs cleaning and how to carry out the cleaning process!

I. Calculation of Temperature Difference for Shell-and-Tube Evaporators
The key focus areas for cleaning shell-and-tube evaporators include the inlet and outlet temperatures of chilled water, the inlet and outlet temperatures of cooling water, condensing pressure, and evaporating pressure. If the condensing temperature and evaporating temperature can be monitored via a touch screen, these values will correspond to the respective condensing saturation temperature and evaporating saturation temperature. The terminal temperature difference can be calculated, and the condensing and evaporating pressures can be converted into their corresponding condensing saturation temperatures and evaporating saturation temperatures.
In addition, you can also observe the color of the copper tubes in the shell-and-tube evaporator. If you can no longer see the original color of the copper tubes, it means that scaling has become severe and they need to be cleaned immediately.
II. Main Methods and Operations for Cleaning Shell-and-Tube Evaporators
There are mainly three methods for removing scale from shell-and-tube evaporators.
Mechanical descaling method
Chemical Acid Pickling for Scale Removal
Electronic water descaling method
Introduce methods for cleaning these three types of stains.
1. Mechanical decontamination:
When using a flexible-shaft cleaning machine—commonly known as the "shipgun machine"—to remove scale from cooling tubes in a condenser, a Ghatotkacha-type shell-and-tube condenser is employed. (Speaking of which, the editor recalls vividly the scene from many years ago when I was holding a gun barrel and manually cleaning the condenser with a manual gun-cleaning tool.)
Principle and Method of Flexible Shaft Cleaning Machines:
The umbrella-shaped scraper, connected to the flexible shaft cleaning machine, simultaneously directs the removed scale, rust, and other contaminants into the flow of water. During the cleaning process, it is important to select an appropriately sized roller blade based on the thickness of the condenser fouling, the degree of corrosion on the tube walls, and the length of service life. To avoid damaging the tube walls during cleaning, use a rotating roller to remove fouling from top to bottom inside the condenser’s vertical tubes. The heat generated by the friction between the scraper and the tube walls is cooled by circulating cooling water. A second cleaning pass should be performed using a roller blade whose diameter closely matches the inner diameter of the cooling tubes.
2. Chemical acid pickling for scale removal:
The chemical acid cleaning method for scale removal is suitable for both vertical and horizontal shell-and-tube condensers (steel tubes). During the dust removal process, the normal operation of the condenser must be halted to ensure safety.
Principle and Methods of Chemical Acid Pickling for Descaling:
Clean and descale the condenser using a prepared, mildly acidic descaling agent. Prepare the descaling solution in the acid cleaning tank, then start the acid-cleaning pump. After the descaling solution has circulated through the condenser’s cooling tubes for 24 hours, close the following valves: the condenser’s inlet air valve, hot-water outlet valve, balance valve, mixed-gas valve, and drain valve. Once the acid-cleaning pump has stopped working, repeatedly flush the pipelines with clean water to remove any residual descaling solution. Then, stop the operation of the condenser’s cooling water pump. Inspect the descaling condition to determine whether further cleaning is necessary; typically, after 24 hours, the descaling should be essentially complete. Continue the process until the condenser is thoroughly cleaned.
3. Electronic Magnetic Water Scaling Prevention Method: The electronic magnetic water scaling prevention method is suitable for various types of condensers. This method not only effectively prevents the formation of new scale but also removes existing scale and provides preventive scaling measures without disrupting the normal operation of the refrigeration system.
The working principle of an electronic magnetic water conditioner:
The calcium, magnesium, and other salts dissolved in the cooling water flowing through the condenser remain in aqueous solution as positive and negative ions at room temperature. As their charge states change, the electrostatic attraction between ions is disrupted. When the cooling water flows at a certain velocity through the transverse magnetic field of the magnetic water conditioner, the dissolved calcium, magnesium, and other ions acquire induced electrical energy.
The above introduces the methods and procedures for determining and performing cleaning of shell-and-tube evaporators. Acid cleaning and mechanical descaling require stopping the normal operation of the refrigeration system. The electronic magnetic water treatment method for scale removal is simple, involves low labor intensity, is unlikely to damage the tube walls in the condenser, and can be carried out at any time. It should be scheduled during the off-season of production.
Miss Deng:18922776417
Mr. Huang:13450460020
Mr. Zhang:13922978523
Email:1536214764@qq.com/ 673047694@qq.com
Company Address: No. 15, Alley 2, North of Lianhe Road, Fulong Village, Shipai Town, Dongguan City
Copyright © 2021 Dongguan Ganghui Refrigeration & Mechanical Equipment Co., Ltd.
Power by:www.300.cn | SEO | Privacy Policy
Welcome to the official website of GangHui!